Timing diagrams of the running commands according to the type of system.
Installations with Inverter FUJI LM2
Up direction

Down direction


Down direction

Hydraulic Lifts – Motor contactors
Direct

(T on) = Contactor’s Time Activation, check on cco feedbacks
(*) Signal feedback for start Valve UP command
Soft Starter

(T on) = Contactor’s Time Activation, check on cco feedbacks
(*) Signal feedback for start Valve UP command
(**) Signal feedback from Soft Starter Deceleration (Soft Stop)
Star Delta

(T on) = Contactor’s Time Activation, check on cco feedbacks
(T on) = Contactor’s Time Disactivation, check on cco feedbacks
(*) Signal feedback for start Valve UP command
Hydro & VVF

(T on) = Contactor’s Time Activation, check on cco feedbacks
(*) Signal feedback for start Valve UP comma

(T on) = Contactor’s Time Activation, check on cco feedbacks
(*) Signal feedback for start Valve UP command
Soft Starter

(T on) = Contactor’s Time Activation, check on cco feedbacks
(*) Signal feedback for start Valve UP command
(**) Signal feedback from Soft Starter Deceleration (Soft Stop)
Star Delta

(T on) = Contactor’s Time Activation, check on cco feedbacks
(T on) = Contactor’s Time Disactivation, check on cco feedbacks
(*) Signal feedback for start Valve UP command
Hydro & VVF

(T on) = Contactor’s Time Activation, check on cco feedbacks
(*) Signal feedback for start Valve UP comma
Hydraulic Lifts – Valves controls
Monitor UCM = 30…39 (2 Valves / 3 Valves / BLAIN EV100 / GMV T3010 / MORIS CM 320 / OMARLift)
(*) In case of Soft Stop use CV1 for UP Valve’s Contactor
(*) in case of no Soft Stop use CV4 for UP Valve’s Contactor – Tstop = BRK-DIR + 1,5s
3 Valve => No Double Valve Down test (A3 Valve Down couldn’t be present)
3 Valves + A3 => Double Valve Down test
Monitor UCM = 40…44 (GMV NGV)

No Double Valve Down test
Monitor UCM = 45…49 (GMV NGV A3)
(*) Valve commands starts only if RDY signal is active
Note: Motor Contactors Starts Only With RUN Feedback Signal
(*) Valve commands starts only if RDY signal is active
Monitor UCM = 50…59 (BUCHER LRV / BUCHER NTA-2 / BUCHER NTA-2 + DSV A3)

LRV1 + NTA-2 ► No Double Valve Down test (A3 Valve Down couldn’t be present)
LRV1 + NTA-2 + A3 ► Double Valve Down test

Monitor UCM = 60…64 (BUCHER i-VALVE / BUCHER iCON-2)

Monitor of Signal + SMA

Monitor of Signal + SMA

Monitor UCM = 65…74 (START ELEVATOR 93/E-2DS)
(**) Signal feedback from Soft Starter Acceleration (Y-BRKS)
CV1 = Used only with 93/E-SL valves (Soft Stop with delay BRK-DIR)
CV4 = Used only with 93/E-2DS valves (Soft Stop)
3 Valves => No double valve down test (A3 valve down couldn’t be present)
3 valves + A3 => Double valve down test
Monitor UCM = 75…79 (ALGI AZRS 2.0)

(*) BRK-DIR = 0,0 s when “soft STOP” is not requested / BRK-DIR = 0,7 s for “soft STOP”.


Monitor UCM = 80…89
(GMV 3010 2CH – GMV 3010 2CH/S – GMV 3010 2CH + DLV – GMV 3010 2CH/S + DLV)
(*) In case of Soft Stop use CV1 for UP Valve’s contactor
(*) In case of no Soft Stop use CV4 for UP Valve’s contactor – Tstop = BRK + 1,5s
3 Valves => No double valve down test (A3 valve down couldn’t be present)
3 valves + A3 => Double valve down test
Monitor UCM = 95…99
(HEVOS He 100/250/650 with SCH001)
(*) Motor contactors starts only with AVV feedback signal
(**) Valve ERS power supply mantained after stop with AVV signal (AVV + RDY < 2s)
(***) Valve ERS power supply mantained after AVV with RDY signal (AVV + RDY < 2s)
NOTE: Valve commands starts only if RDY signal is active
Monitor of Signal RDY
(***) Valve ERS+ENR power supply mantained after stop with RDY signal (RDY < 2s)
NOTE: Valve commands starts only if RDY signal is active
Monitor of Signal RDY

(*) In case of Soft Stop use CV1 for UP Valve’s Contactor(*) in case of no Soft Stop use CV4 for UP Valve’s Contactor – Tstop = BRK-DIR + 1,5s
3 Valve => No Double Valve Down test (A3 Valve Down couldn’t be present)3 Valves + A3 => Double Valve Down test
Monitor UCM = 40…44 (GMV NGV)

No Double Valve Down testMonitor UCM = 45…49 (GMV NGV A3)
(*) Valve commands starts only if RDY signal is activeNote: Motor Contactors Starts Only With RUN Feedback Signal
(*) Valve commands starts only if RDY signal is active
Monitor UCM = 50…59 (BUCHER LRV / BUCHER NTA-2 / BUCHER NTA-2 + DSV A3)

LRV1 + NTA-2 ► No Double Valve Down test (A3 Valve Down couldn’t be present)LRV1 + NTA-2 + A3 ► Double Valve Down test

Monitor UCM = 60…64 (BUCHER i-VALVE / BUCHER iCON-2)

Monitor of Signal + SMA
Monitor of Signal + SMA
Monitor UCM = 65…74 (START ELEVATOR 93/E-2DS)
(**) Signal feedback from Soft Starter Acceleration (Y-BRKS)CV1 = Used only with 93/E-SL valves (Soft Stop with delay BRK-DIR)
CV4 = Used only with 93/E-2DS valves (Soft Stop)
3 Valves => No double valve down test (A3 valve down couldn’t be present)3 valves + A3 => Double valve down test
Monitor UCM = 75…79 (ALGI AZRS 2.0)

(*) BRK-DIR = 0,0 s when “soft STOP” is not requested / BRK-DIR = 0,7 s for “soft STOP”.


Monitor UCM = 80…89
(GMV 3010 2CH – GMV 3010 2CH/S – GMV 3010 2CH + DLV – GMV 3010 2CH/S + DLV)
(*) In case of Soft Stop use CV1 for UP Valve’s contactor(*) In case of no Soft Stop use CV4 for UP Valve’s contactor – Tstop = BRK + 1,5s
3 Valves => No double valve down test (A3 valve down couldn’t be present)3 valves + A3 => Double valve down test
Monitor UCM = 95…99
(HEVOS He 100/250/650 with SCH001)
(*) Motor contactors starts only with AVV feedback signal(**) Valve ERS power supply mantained after stop with AVV signal (AVV + RDY < 2s)
(***) Valve ERS power supply mantained after AVV with RDY signal (AVV + RDY < 2s)
NOTE: Valve commands starts only if RDY signal is active
Monitor of Signal RDY
(***) Valve ERS+ENR power supply mantained after stop with RDY signal (RDY < 2s)NOTE: Valve commands starts only if RDY signal is active
Monitor of Signal RDY