Pitagora 4.0 – Rollback control and comfort adjustment


When the Pitagora controller is applied to installations equipped with closed loop gearless machines, comfort and precision can be optimized thus avoiding undesired effects such as rollback (typical of lifts with unbalanced load).
The following parameters can be adjusted to achieve optimal setting for your installation. It is suggested to follow the procedure from start to end in the proposed sequence.

.

Starting phase adjustments

ParameterDescriptionSuggested adjustmentsDefault
GearedGearless
F24Starting speed holding timeDo not change this value, unless the installation is equipped with digital positioning system
(Magnetic readers)
0,20,2
H64Zero speed control timeSet value between 0,7 and 0,8 then increase to soften start phase ramp.
Important: Enter the "Positioning" Menu and check parameters DIR-BRK (must be kept low:
0,1-0,2) and BRK-S (must be kept higher than H64)
0,80,8
H65Soft Starter activationDo not change this value0,50,5
L66RBC activation time at zero speed
(Specifies the maximum time length for estimating an unbalanced load)
Do not change this value2 s.2 s.
L68RBC Proportional Gain (P constant)
(specifies the P constant of the Automatic Speed Regulator to be used
during RBC calculation time)
Motor overshoots: increase value by 0,25
Vibrations: decrease value by 0,25
101,8
L69RBC Integral Time (I constant)
(specifies the I constant of the Automatic Speed Regulator to be used
during RBC calculation time)
Motor overshoots: decrease value by 0,001
Vibrations: increase value by 0,001
0,010 s.0,0003 s.
L73Unbalanced load compensation
(specifies the I constant of the Automatic Position Regulator to be used
during RBC calculation time)
Motor overshoots: increase value by 0,50
Vibrations: decrease value by 0,50
00,5
L05Proportional gain current loop starting phaseIt depends on the type of machine1,51,5
L80Brake Control (Mode)Do not change this value11
L82ON delay time
(specifies the delay time during which the inverter main circuit is kept activated)
Larger Brakes: decrease value by 0,1
Smaller brakes: increase value by 0,1
0,2 s.0,2 s.

High speed phase adjustments

ParameterDescriptionSuggested adjustmentsDefault
GearedGearless
L36P" Gain constant at high speedSpeed fluctuations: increase value by 0,25
Vibrations: decrease value by 0,25
102
L37I" Time I constant at high speedSpeed fluctuations: decrease value by 0,01
Vibrations: increase value by 0,01
0,100 S.0,100 S.

Low speed adjustments

ParameterDescriptionSuggested adjustmentsDefault
GearedGearless
L38P" Gain constant at low speedMotor stops: increase value by 0,25
Vibrations: decrease value by 0,25
102
L39I" Time I constant at low speedMotor stops: decrease value by 0,01
Vibrations: increase value by 0,01
0,100 S.0,100 S.

Stopping phase adjustments

ParameterDescriptionSuggested adjustmentsDefault
GearedGearless
F25DC Brake Parameters
Stop Speed
Do not change this value0,10,1
L38"P" Gain constant at low speedCar unable to stay at floor: increase value by 0,25
Vibrations: decrease value by 0,25
102
L39"I" Time I constant at low speedCar unable to stay at floor: decrease value by 0,01
Vibrations: increase value by 0,01
0,100 s.0,100 s.
H67Stop speed holding timeCar unable to stay at floor: increase value by 0,25 (Max: 1,0 s)
Important: Enter the "Positioning" Menu and check parameters BRK- DIR (must be kept at 2 s)
and Stopping Boost (set between 1% and 2%)
1,5 s.1,5 s.
L80Brake Control (Mode)Do not change this value11
L82ON delay time
(specifies the delay time during which the inverter main circuit is kept activated)
Larger Brakes: decrease value by 0,1
Smaller brakes: increase value by 0,1
0,20,2
L83Brake Control (OFF delay time)
(specifies the delay time between stop speed and turning off of the brake signal)
Larger Brakes: decrease value by 0,1
Smaller brakes: increase value by 0,1
0,1 s.0,3 s.
E16Deceleration time # 9 (Last deceleration ramp)Increase value by 0,5 to soften last ramp (max suggested value: 3 sec)1,80 s.1,80 s

Case VVVF controllers with non-encoder based positioning systems

ParameterDescriptionSuggested adjustmentsDefault
GearedGearless
F24Starting speed holding timeSet value between 0,7 and 0,810,1
E12Acceleration at high speedSpeed fluctuations: increase value by 0,2522
E13Acceleration at low speedMotor stops: increase value by 0,2520,100 s.
C07Creep Speed (10% of high speed)Motor stops: increase value by 0,1
Vibrations: increase/decrease value by 0,1
1,5 s.
C11High SpeedIf the car is unable to keep floor level, make sure the low speed phase is performed correctly by
reducing high speed C11 to half of its value to check that low speed is kept for few seconds,
then slowly increase C11.
See
Nominal Value
on the motor plate