1. Home
  2. Electric Systems
  3. Pitagora 4.0
  4. Pitagora 4.0 – Parameters menu

Pitagora 4.0 – Parameters menu


Integrated Programming Module
The Motherboard has an integrated programming module that allows viewing and editing of all the basic parameters for the controller management and configuration. In VVVF’s version, also FUJI’s parameters of the basic (menu VVVF BASE) and advanced (VVVF ADVANCED menu) configuration may be viewed and edited.

Functionality of the programming keys

Menu navigation keys and parameter selection keys.
Menu depth navigation keys (forward and backward).
OK button: Key to access the selected menu and to confirm the selected parameter.
ESC button: Returns one level back in the menu.

Programming menu and Changing system parameters

Access to the programming menu

Access the ‘Emulation’ menu to configure the programming parameters.

Configuration menu

CodeParameter nameParameter description
A1Temporary operationsActivation of the Temporary Operation mode of the system
A2Test & measuresAutomatic tests to facilitate the final checks before the system is put in normal service
A3Acces Code ?Definition of a passcode to access the setup Menu
A4Type of wiringType of wiring configuration between controller and cabin / floors
A5Type of controlType of control for the lift and collection mode
A6Type of tractionTraction VVVF or Hydraulic lift (Direct start / soft starter / Star delta)
A7No. of floorsNumber of floors of the installation
A8Re-levellingParameter that activates and manages the Relevelling manoeuvre (mandatory for hydraulic systems, optional for VVVF systems)
A9Main floorPosition of the main floor (all calls below this floor are served only upwards if down collective)
A10Low speed fault timeTime before activation of the Low Speed fault (Fault #3)
A11Running time:Time before activation of running time fault #26-27
A12Calls with 16IO boardParameter that defines the mode of use of the 16IO terminal board in the case of terminal cabin connections:
1) 16IO A board: the 16IO board is used as the only interface board in the panel, to manage the terminal cabin calls (12 floors max)
2) 16IO B board: the 16IO board is used as the second interface board in the panel, to manage the terminal cabin calls (12 floors max)
3) 16IO A+B board: two 16IO boards are used simultaneously to manage the terminal cabin calls (28 floors max)
A13Group operationType of group operation (Simplex / Multiplex / Multiplex light)
A14Multiplex ConfigurationParameters for Multiplex configuration.
Elevator position in the Group;
Push-Buttons Line;
Multiplex floors;
Multiplex Offset;
Long press multiplex call;
A15Multiplex CallIn multiplex installations a floor call can be differentiated with a long push-button pressure (more than 3 seconds) calling:
a) The installation with lower “Lift No (LN)” parameter (for example if there is a duplex installation with a big cabin for disabled passengers and a smaller one, the greater must be set as “1” and the other as “2”;
b) In an “asymmetric floor distribution” system, the installation that can reach the lowest/highest level.

Doors menu

CodeParameter nameParameter description
D0Retiring cam activation delayDelay before activation of the retiring ramp
D1Retiring cam deactivation delayDelay before deactivation of the retiring ramp
D2Lock fault delayDelay before the activation of the door lock fault (Fault #9)
D3Door opening delayDelay before auutomatic door opening (upon arrival at floor)
D4Parking time with open doorsParking time at floors with open doors before door close command
D5Door closing delayDelay before door closes in case of registered calls 
D6Access modeNumber of accesses and door opening logic
D7Type Door ADoor type for entrance A:
1) Full automatic: cabin+floor automatic doors;
2) Car automatic: manual doors at floors, automatic cabin doors;
3) Manual: manual doors at floors, car doors manual or not present;
3) Car independent: manual doors at floors, car doors independent;
D8Door A with limit switchPresence of a limit switch for door A (not present for manual and independent doors)
D9Access layout Side AAccess layout for Side A of the installation: access to each floor and (for automatic doors) type of parking (with doors open or closed).
“NO”: permanent exclusion of the access from the total count of stops
“Not enabled”: temporary exclusion of the access.
D10Door A Open/Close timeDoor opening/closing operation completion time (Doors without limit switches)
D11Door A poweredDoor A constantly powered during the run (door close) or at floor (door open)
D12Type Door BSelection of door type for entrance B (see Type Door A):
D13Door B with limit switchPresence of a limit switch for door B (not present for manual and independent doors)
D14Access layout Side BAccess layout for Side B of the installation: access to each floor and (for automatic doors) type of parking (with doors open or closed).
“NO”: permanent exclusion of the access from the total count of stops
“Not enabled”: temporary exclusion of the access.
D15Door B Open/Close timeDoor opening/closing operation completion time (Doors without limit switches)
D16Door B poweredDoor B constantly powered during the run (door close) or at floor (door open)
D17Advance openingEarly door opening (before the cabin stops)
D18Photocell typeParameter to select the type of photocell:
NO photocell: contact opens if the beam is free. The contact closes if the beam is interrupted. The shock, photocell and open door contacts must be wired in parallel.
NC photocell: opposite of the NO photocell. The shock, photocell and open door contacts must be wired in series.
NOTE: The shock, photocell and open door contacts must all be of the same kind (NO or NC)
D19Door contact delayDelay before start (to compensate for any bounces from worn safety contacts)

Signals menu

CodeParameter nameParameter description
Delay end priorityPriority mode holding time before reactivating floor or cabin calls.
If the CABIN PRIORITY function is activated (from DMCPIT card input): System waiting time, after deactivation of the function, before recording a floor call again.
If the LOP PRIORITY function is activated (from BDU input): System waiting time, after deactivation of the function, before recording a cabin/floor call again.
Note: in systems with UNIVERSAL operation, this parameter defines the time spent in the BUSY state.
LOP feedbackEnables the blinking mode for floor buttons upon registration
AUX outputsSet up of the auxiliary outputs of the 16 RL cards (if present) and the BDUs. The settings must be made progressively, first RL-1 then RL-2 then BDU.
Outputs available for the RL-1 Card: 1 wire/floor display / “Car at floor” signal / Floor light / Gray display / 9 segment display / “Car coming” signal / 1 wire/floor HYD
Outputs available for the RL-2 Card: “Car at floor” signal / Floor light / Gray display / 9 segment display / “Car coming” signal
Combinations of OUT-1 and OUT-2 outputs for the BDUs:
Type 0 = Car at floor + Out of Service
Type 1 = Up arrow + Down arrow
Type 2 = Car at floor + Car coming
Type 3 = Car at floor + 3 Wire Display
Note: The configuration is first generic and then specific for each floor (example arrows to all floors and 3 wire display to main floor).
See DIDO for details.
Automatic floor designationThis parameter defines the numerical value associated with the piano assigned to the bottom of the piano (“Floor 0”). The serial display automatically indicates an incremental number at every subsequent floor.
Manual floor designationManual setting of alphanumeric characters for serial position indicators. Setting must be done for each floor
Trigger on PVParameter that activates the trigger for speech synthesis / next direction arrows at the slowdown point (Yes) or upon arrival at the floor (No).
Next direction arrowsParameter that activates the trigger for speech synthesis / next direction arrows at the slowdown point (Yes) or upon arrival at the floor (No).
Cabin light timerTimer for the light in the cabin after arriving at the floor.
With the parameter set at 0s the timer is not active (light always on).
Delay EMEMultiparameter for Automatic return to floor in emergency (See https://dido.dmg.it/it/knowledge-base/p40-emergency-operations/).
Value #1: Type of automatic return:
Type A = return to the nearest floor (Emergency 81.20 and 81.1 with UPS)
Type B = return to the nearest floor (Integrated emergency for gearless 81.20)
Type C = return to the floor defined as MAIN (Emergency 81.20 and 81.1 with UPS)
Type D = specific evacuation maneuver for elevators on ships (RNO).
Value 2: Delay before starting the Emergency maneuver (from IEME power failure signal).
Note: in hydraulic systems the descent is always at the lowest level
Buzzer 81-21Activation of the EN81.20 acoustic signal (door bypass) also to indicate the presence of inactive 81.21 protections in systems with reduced pit/headroom.
Ship FunctionsEnabling of special functions dedicated to elevators installed on cruise ships.
Beep at stopEnables a beep warning signal in the cabin keypad when the elevator arrives at the floor.

Special features menu

CodeParameter nameParameter description
Reset DirectionDirection of travel during the reset procedure
Traveling limits in inspection(Only for magnetic readers positioning system)
Defines the travelling limits during inspection mode.
If set on “Beyond AGB/AGH”, the controller does not allow any movement beyond top/bottom floors.
Fire-fighters OperationsFor lifts that include the Fire-Fighter Operation, this multiple parameter defines the type of fire fire operation and the related settings for each floor (recall side, type of POM and CPOM key contacts).
Fire detectionParameter for fire detection at floors.
if the lift is at a different floor than the one where fire was detected, all registered calls from/to this floor are cancelled;
if the lift is at the floor where fire was detected, the controller blocks door opening, closes doors (if open upon fire detection) and sends the car to a safe floor
Stop button registrationThe system registers the out of service mode (pressure of STOP button).
It is also possible to set the delay to avoid simultaneous movement in installations powered with a generator.
EN 81-20Parameter that configures the system according to the EN 81-20 standard. If set to “YES” the following are enabled:
the inspection button panel from the bottom of the pit;
the access control in the pit;
the control of the presence of the UCM;
the monitor of the second contact of the cabin doors;
the door photocell with NC (normally closed) contact
Anti-nuisance optionOption that limits unauthorized activations. The value defines the maximum number of stops without cutting the photocell (for automatic doors) or opening the door (manual) beyond which all calls from the cabin are cancelled
Out of Service floorDestination floor for Lift out of service (HS input activated).
Automatic return to floorMultiple parameter for the Automatic Return to Floor manouever. Defines the return flow and the minimum waiting time before activation of the automatic return 
Return zonesAdvanced settings for return at floor at planned hours / days:
-) Day (0 = everyday, 1 = monday … 7 = sunday);
-) Selected time interval (4 interval each day);
-) Return floor;
-) Start time;
-) End time (max time: 7h 45 min);
R. zone timingTiming for selected return zones
Call erasing at floorCancellation of calls to the floor where the cabin stops, without checking the direction of travel (option valid only for full collective operation)
Drift control (France)Drift control (NF P82-212)
Cabin call access code / PenthouseAllows you to define a 4-digit code to enable a cabin call. This option can be enabled for every floor, identified by the labels BC0…BC27.
See the “Access Protection” page on DIDO for operating details.
Note: Entering the code “0 _ _ _ ” enables the PentHouse function for that floor.
Machine room temperature checkEnables the control of the ambient temperature in the machine room through the relative sensor (if present). If the temperature goes outside the minimum and maximum thresholds set for a time greater than 30 seconds, the system stops at a floor and error 39 “”Ambient temperature”” appears. In addition to setting the two thresholds, it is necessary to set the ambient temperature, confirming or modifying the one detected.
Note: The control is active only in normal operation or Cabin priority.
Automatic CallsEnables an automatic test mode that simulates up to 120 calls at programmable intervals between 10 s and 60 s. It is also possible to enable or disable the door opening (if enabled, the system will also accept floor calls while still simulating scheduled calls).
The function is automatically terminated when the system is turned off and/or the system is put in Inspection mode
Monitor UCMUCMP Management Solution
UCMInstallation type 81-1 / 81-20 / 81-21
Shaft access procedure and Protections.
Forced StopParameter that defines a floor as forced. If activated, the system will stop at that floor at each passage.
Protected floorParameter that defines a floor as protected in combination with the “Live+” function. Upon arrival at the protected floor, the doors open only with explicit consent (pressing the door opener button), otherwise the system returns to the previous floor.
LOP PriorityEnables the floor priority call function. Needs the Pitagora 16 I/O card
(or keyswitch input from floor BDU)
Enable floorCall enabling function (e.g. CARD Reader). Requires the auxiliary 16 I/O card.
Type 1: LOP enable: to enable calls, the corresponding input of the 16 I/O card must be closed.
Type 2: COP enabling To enable calls, the corresponding input of the 16 I/O card must be closed
Type 3: Enable COP + LOP: to enable calls, the corresponding input of the 16 I/O card must be closed (disabling the floor)
Shaft ProtectionEnables the shaft access protection circuit (EN81-20)
Integrated Load WeighingEnable the built-in load weighing function. Requires a calibration procedure (Test 22)

Positioning menu

– With magnetic readers –

CodeParameter nameParameter description
Positioning systemType of positioning system: with Encoder or traditional. Note: Can only be modified in Temporary Oper. Mode
AutosettingStart of floor position self-learning procedure. Can only be modified in Temporary Operation mode.
Floor PositionPosition value for each floor
Accel. TimeAcceleration time. Time required to switch from start speed to travelling speed.
Starting BoostStarting speed
Stopping BoostFinal (stopping) speed
Max speedMaximum speed during the travel
Inspection SpeedTravelling speed in inspection mode 
AGB/AGH speedTravelling speed on AGB/AGH limit points. Same speed adopted during emergency operations
Delay Dir.-BRKVVVF: Delay between activation of travel direction and BRK command (start)
OLEO: Star / Delta delay
Delay BRK-SDelay between activation of BRK command and beginning of the analogic speed ramp
Delay BRK-Dir.Delay between deactivation of run command and deactivation of travelling direction (stop at floor)
Emergency BRK ONEmergency break modulation parameter
Emergency BRK OFFEmergency break modulation parameter
Monitor EncoderContains information on:
Encoder features, reading of slowdown heights (R1D / R1S), re-levelling (RRIPD / RRIPS) and stop of the cabin (RLD / RLS) where D indicates down while S means up; finally it contains info on reading AGB / AGH and ZP heights.
Note: R1D and R1S heights can be modified pushing Enter without repeating self learning procedure (to let the slowing down distance be equal in rise and descent).
ZP lenght

– With encoder –

CodeParameter nameParameter description
Positioning systemType of positioning system: with Encoder or traditional. Can only be modified in Temporary Oper. Mode
Note: in case of absolute Encoder and shaft lengths longer than 65 meters change the resolution of Encoder = 2 in autosetting menu before starts the Manual teach procedure.
Top PVPosition of the deceleration (passage in Low Speed) and number of entrances
PV at floorsPosition of the specific deceleration for each floor
Short level delayTime before short level deceleration (only if a short level is programmed)
Delay Top PV 2Delay before passage to Intermediate speed
Delay Dir.-BRKVVVF: Delay between activation of travel direction and run command (BRK)
OLEO: Star / Delta delay
Delay BRK-SDelay between activation of BRK command and speed command
Delay BRK-Dir.Delay between deactivation of run command and deactivation of travel direction (arrive at floor)
Inspection speedSets the speed of travel in inspection
Emergency BRK OnEmergency break modulation parameter (modify only if EME board is not present)
Emergency BRK OffEmergency break modulation parameter (modify only if EME board is not present)

VVVF Basic menu

CodeParameter nameParameter description
F03Maximum speedMax speed of the motor 
F05Rated VoltageRated voltage of the motor driven by the inverter 
F07Acc T1Acceleration ramp (Only with FAI/FAS positioning system)
F08Dec T2Acceleration ramp (Only with FAI/FAS positioning system)
F42Control ModeControl Mode
E12Acc/dec Time  5
E13Acc/dec Time  6
E15Acc/dec Time  8
E16Acc/dec Time  9
C07Creep SpeedCreeping speed (Only with FAI/FAS positioning system)
C10Middle SpeedSystem speed under inspection mode (Only with FAI/FAS positioning system)
C11High SpeedHigh speed for multistep speed change (Only with FAI/FAS positioning system)
P01Motor PolesNumber of poles of the motor
P02Motor Rated CapRated power of the motor
P03Motor Rated CurRated current intensity of the motor
P04Motor AutotuningAuto tuning of motor parameters (geared drives only)
P06M-No-Load Curr.Motor no-load current
P12M-Rated SlipRated slip frequency of the motor
L01PG select
L02PG resolutionResolution of the pulse encoder (Pulse/ Turn)
L19S-Curve 1S-Curve – 1 
L24S-Curve 6S-Curve – 6
L25S-Curve 7S-Curve – 7
L26S-Curve 8S-Curve – 8
L27S-Curve 9S-Curve – 9
L82Brake On DelayDelay from activation of BRKS output
L83Brake Off delayDelay from deactivation of BRKS output

VVVF Advanced menu

CodeParameter nameParameter description
F01Speed commandCommand selection for speed variation 
F03Maximum speedMax speed of the motor 
F04Rated speedRated speed of the motor (Frequency)
F05Rated VoltageRated voltage of the motor driven by the inverter 
F07Acc T1Acceleration ramp (Only with FAI/FAS positioning system)
F08Dec T2Acceleration ramp (Only with FAI/FAS positioning system)
F09TRQ BoostTorque increase
F10Electronic OLOverload electrical protection
F11Overload LevelElectronic Thermal Overload Protection for Motor (Value in Ampere equal to the inverter size)
F12Overload timeThermic time constant
F20DCBrake speedFrequency threshold for DC INJECTION
F21DC Brake levelIntensity threshold for DC INJECTION
F22DC Brake TDC INJECTION time
F23Starting SpeedStarting speed (in Hz) for the inverter
F24Holding TimeHolding time of running at starting speed for the inverter
F25Stopping SpeedStopping speed (in Hz) for the inverter
F26Motor SoundCarrier frequency
F42Control ModeControl Mode
F44Current LimiterActivation level of the current limiter.
% to the rated current of the inverter.
If “Auto”, value means no current limitation
E04Command X4Input X4 not used
E05Command X5Input X5 not used
E06Command X6Input X6 not used
E07Command X7Input X7 not used
E08Command X8Input X8 not used
E10Acc/dec Time 3
E11Acc/dec Time 4
E12Acc/dec Time  5
E13Acc/dec Time  6
E14Acc/dec Time  7
E15Acc/dec Time  8
E16Acc/dec Time  9
E20Signal Y1Output Y1 (transistor) not used
E21Signal Y2Output Y2 (transistor) not used
E22Signal Y3Output Y3 (transistor) not used
E23Signal Y4Output Y4 (transistor) not used
E30Speed Arr. HystNot used
E31Speed Det.LevNot used
E32Speed Det HystNot used
E39RRD LevelRecommended direction in emergency  (Not used)
E61Analog Input 12Function of analog input 12
E98Command FWDFunction for screw terminal FWD
E99Command REVFunction for screw terminal REV
C01BATRY TL i“Torque limitation in emergency.
If “OFF”, value means no current limitation”
C02BATRY TL t
C03Battery SpeedSpeed during emergency run 
C07Creep SpeedCreeping speed (Only with FAI/FAS positioning system)
C10Middle SpeedSystem speed under inspection mode (Only with FAI/FAS positioning system)
C11High SpeedHigh speed for multistep speed change (Only with FAI/FAS positioning system)
P01Motor PolesNumber of poles of the motor
P02Motor Rated CapRated power of the motor
P03Motor Rated CurRated current intensity of the motor
P04Motor AutotuningAuto tuning of motor parameters (geared drives only)
P06M-No-Load Curr.Motor no-load current
P07M-%R1Motor (%R1)
P08M-%XMotor (%X)
P09M-Slip driving Slip compensation gain in percentage to the rated slip (P12) at the driving sides
P10M-Slip brakingSlip compensation gain in percentage to the rated slip (P12) at the braking sides
P11M-Slip TSlip compensation time value (fixed)
P12M-Rated SlipRated slip frequency of the motor
P60Armature Resistance – Rs
P62Armature q-axis reactance – Xs
P63Interphase Inductive Voltage – E
P65q-axis inductance magnetic saturation correction
H04Auto reset TimesAuto-resetting (Number of times)
H05Auto reset intAuto-resetting (Reset interval)
H06Cooling Fan CTRL“Delay on Cooling Fan turning off
(Auto value means that there is no limit on fan control; fan is always turned on)”
H56
H57S-Curve 11Curve to S-11
H58S-Curve 12Curve to S-12
H64Zero Hold Time
H65Soft Start Time
H67Stop Hold Time
H96Brake MonitorEnable Brake monitor
H190Motor UVW orderSequenza fasi uscita motore
L01PG select
L02PG resolutionResolution of the pulse encoder (Pulse/ Turn)
L03P.P.Tuning
L04P.P.OffsetMagnetic Pole Position Offset (Offset angle) for gearless drives
L05ACR P gain
L07Automatic pole tuning selection
L19S-Curve 1S-Curve – 1 
L20S-Curve 2S-Curve – 2
L21S-Curve 3S-Curve – 3
L22S-Curve 4S-Curve – 4
L23S-Curve 5S-Curve – 5
L24S-Curve 6S-Curve – 6
L25S-Curve 7S-Curve – 7
L26S-Curve 8S-Curve – 8
L27S-Curve 9S-Curve – 9
L28S-Curve 10
L29SFO Hold T“Short Floor Operation (Holding time)
Only used for FAI-FAS positioning mode”
L30SFO SpeedShort Floor Operation (Allowable speed) – NOT USED
L36ASR P Gain High
L37ASR I Gain High
L38ASR P Gain Low
L39ASR  I Gain Low
L40Switch Speed 1Not used
L41Switch Speed 2Not used
L42ASR-FF Gain
L55TB Start time
L56TB End time
L64TB Digital 3
L65ULC operationUnbalanced load Compensation 
L66ULC activationUnbalanced load compensation (Activation time)
L68ULC ASR P gain
L69ULC ASR I gain
L73APR P gain zero
L74APR D Gain
L75Filter Time
L76ACR P constant
L80Brake modeBrake Control (BRKS) output mode
L81Brake On LevelOutput current that turns the BRKS signal ON when L80 = 2.
L82Brake On DelayDelay from activation of BRKS output
L83Brake Off delayDelay from deactivation of BRKS output
L84BRKS check tAllowable time between BRKS output and BRKE input (Er6) 
L99ACTION SELNot used
L122Del. Op. Input Power Det. Level
L124Del. Op. Dir. Calc. Delay Timer
L130Sheave diameter (Ds)
L131Encoder diameter (De)
L132Theta compensation band
L133Theta compensation gain lower limiter
L134Backlash Time“Backlash Time
(When L65 = 2)”
L198Op. set switch 1BIT0 = It is possible to fix the carrier frequency to 16 kHz for the whole speed range in order to reduce driving noise.
L199Op. set switch 2Reserved

Updated on 15 Aprile 2025
Was this article helpful?

Related Articles

dido.dmg.it
Learn more

Cookies Policy